Drawing power from a vehicle battery in scavenge mode has the potential to overdischarge the
vehicle starter battery rapidly. Run the vehicle motor when scavenging power from a vehicle to avoid
overdischarging the starter battery.
Beware of HyPR overheating when using the power scavenging function.
Power input is limited to 150 W. Power output is limited to 100 W. Custom cables may be required.
If the load exceeds 100 W, the power supply will temporarily shut down and will not resume until
the load is reduced. The 9-36 VDC switch on the Faceplate is unlikely to trip due to the fact that the
Scavenger power supply and the inverter self protect.
Auto Generator Start / Stop
The HyPR Auto Generator Start/Stop (AGS) functions are controlled using the GENERATOR
CONTROL switches on the Faceplate.
• The ON position turns on a connected generator regardless of the DC bus voltage.
• The AUTO setting automatically starts and stops a connected generator based on DC bus
(battery) voltage.
• The OFF setting stops the generator(s) if it is running or prevents the generator from turning on.
Automatic Generator Start/Stop (AGS) voltages
The HyPR AGS is programmed to start and stop the generator(s) at voltages that allow the ESMs to
charge and discharge over a safe and efficient voltage range.
• Generator start set point = 25.5 VDC
• Generator stop set point = 29.0 VDC
The generator start and stop voltage set points are programmable via a TECH PORT on the
Faceplate. Contact Solar Stik Technical Support for assistance if reprogramming is required.