April 2021
|
Solar Stik
®
, Inc.
6
|
24VDC HyPR 3000 Operator and Maintenance Manual
PRELIMINARY DRAFT
HyPR 3000 Capabilities and Controls
The HyPR features specific capabilities for the system in which it is employed and, while many of the
circuits in the HyPR are fully automatic, outside user-established limits, not every HyPR feature may
be used in every application.
Most functions and modes are controlled by programmable settings at the User Interface(s).
• “Functions” are related to specific circuits or hardware in the HyPR.
• “Modes” refer to the operational employment of the HyPR circuits.
The faceplate is divided into two interfaces; the AC and the DC control panels:
• The HyPR AC INTERFACE panel provides complete AC circuit input and output control.
• The HyPR DC INTERFACE panel provides complete DC control, including complete circuit data
and metering.
When the main power breaker switch is turned on:
• The HyPR DC INTERFACE will power up and report DC bus voltage and amperage data on the
home screen.
• The inverter (DC>AC) will be active, but only operational once the HyPR AC OUTPUT breaker is
engaged.
• The converter (AC>DC) will be active, but only operational once the HyPR AC INPUT breaker is
engaged.
• The HyPR solar charge controller will be active, but only able to process PV power once the
SOLAR INPUT breaker is engaged.
• The HyPR DC>DC converter (scavenger) will be active, but only able to process DC power once
the 9-36 VDC INPUT breaker is engaged.
Data Management
• The DC INTERFACE provides complete DC circuit data only when an active PV array is
connected
• The HyPR DC Interface provides basic DC circuit data, including ESM/bus voltage and net
current only when active ESMs are connected.
• If no ESMs are connected to the HyPR, then only the DC bus voltage is available from the HyPR
DC INTERFACE.
• DC bus voltage is the only accurately-reported metric from the HyPR DC INTERFACE when
ESMs are not connected.
User Control Functions