65
June 2020
|
Solar Stik
®
, Inc.
24VDC PRO-Verter 5000-120 AGS Operator Manual
Fault Temp
H1 77F
Fault Temp
H1 D- 1 12:23A
Fault Temp
H1 14.2 VDC
AGS fault
Day(s) since fault
occurred
Fault History
Number
Time fault
occurred
AGS DC voltage
at time of fault
AGS temp sensor
at time of fault
The following is an example describing how to access AGS Faults . The procedure for inverter
and AGS Faults is the same:
Press the SELECT knob, rotate the knob until the 04B AGS Faults menu displays, and then press
the SELECT knob.
04B AGS Faults
This menu displays a history of the last nine AGS faults. Information for each fault displays from the
most recent fault (H1) to the earliest/past recorded faults (H2 up to H9).
Note
: The 04D Clear Faults menu allows all recorded fault history information—for any inverter
and/or AGS, ACLD, or PT controller that is network connected—to be cleared/erased. Refer also
to the TECH: 04 Fault History/04D Clear Faults menu.
See the diagram below. Rotate the SELECT knob to display the second and third screens for the
particular fault shown on the first screen. After viewing all screens for the fault, continue to rotate the
SELECT knob to display earlier faults (as applicable).
• First screen
—The top line displays the AGS fault mode. The bottom line displays the fault
history number, day(s) since this fault occurred, and the time this fault occurred.
• Second screen
—The DC voltage on the AGS at the time of this fault.
• Third screen
– The temperature of the AGS temp sensor at the time of this fault.
TECH: 04 Fault History
Press the SELECT knob, rotate
the knob until the 04B AGS
Faults menu displays, and
then press the SELECT knob.
Fault History (Tech 04)
Tech 04 in the LCD user interface provide provides the fault history for the inverter (04A) and the
AGS (04B). The following is an example of how to read and understand the fault history in 04B AGS
Faults