June 2020
|
Solar Stik
®
, Inc.
70
|
24VDC PRO-Verter 5000-120 AGS Operator Manual
1
Monthly (M)—every month
2
Monthly Plus (M+) — more frequently than monthly as conditions require
Failure to follow these instructions may result in permanent equipment failure and/or
personal injury .
Preventive Maintenance Checks and Services
Part Number
Description
Filter Image
07-1000627
Replacement Air Vent Foam Filter
for PRO-Verters and Power Hubs
(pack of 100)
Spare / Replacement Air Intake Filter
PRO-Verter MAINTENANCE
Item #
Item to be
Inspected
Interval
Procedures
Non-mission Capable
1
Visual
inspection of
24VDC PRO-
Verter 5000
M
1. Inspect case for visible damage
and missing items.
2. Clean excessive dust or dirt
accumulation from the exterior,
interior and connectors.
3. Close all unused port covers.
~If the case is broken or split or
if connectors are damaged, do
not place into service.
2
Air Intake
Filters
M
1
M+
2
1. Remove the three (3) air intake
vent covers to expose the filter
material. (See PRO-Verter Manual
for location of air intake filters.)
2. Wash with water and dry the filter.
Reinstall.
3. If the filter is damaged or cannot
be cleaned replace.
~If the filter cannot be cleaned,
is too damaged to function
properly and a replacement is
not immediately available, the
unit is partially mission capable.
Replace the filter as soon as
possible to restore the unit to
fully mission capable.