24VDC PRO-Verter 5000-120 AGS Operator Manual
Secondary Scrolling Status Messages
These displays alternate with the inverter/charger status to indicate other pertinent messages.
Gen Warm-up
The AGS unit has commanded the generator to run, but the PRO-Verter will not connect to the
generator’s AC output until the generator warm-up time is complete.
Gen Cool Down
The autostop setting (FAVS F5: Gen Run VDC > Set Stop Gen V= 28.8) has been met and the
generator has been disconnected from the PRO-Verter. However, the generator still runs until the
FAVS F5: Gen Run VDC > Set Stop Gen = 1 Minute and cooldown (Setup: 04J) time is met.
Note:
Most faults (inverter, AGS, and BMK) also alternate with the inverter/charger status.
Charger Standby
This indicates the charger has been disabled to prevent further charging, but the AC power (from
utility or generator) to the AC input is still available on the AC output. This display is shown when
the CHARGER ON/OFF button is pressed while the AC power is passing through the inverter/
charger.
Note
: Press the CHARGER ON/OFF button to enable charging again. When enabled, the charger
continues in the previous charge mode and the CHG (green) LED comes on.
Charging
Once Charge mode has been enabled, the unit waits and displays “Charging” to determine the
charge routine.