29
December 2020
|
Solar Stik
®
, Inc.
SYSTEM SETUP AND OPERATION GUIDE FOR THE SOLAR STIK USAF G-BOSS MEDIUM AND HEAVY HYBRID POWER SYSTEM
PRELIMINARY DRAFT
Figure 17. PRO-Verter Faceplate
LCD User Interface
—The LCD screen and the associated buttons and LEDs are used to program
and control the PRO-Verter and to control and monitor the status of the System. The PRO-Verter is
programmed at Solar Stik to meet the specifications of a specific application. Programming mode is
blocked and password protected, but if reprogramming is required it can be accessed by contacting
Solar Stik Technical Support (800-793-4364 Ext. 102; 24 hours a day, 365 days a year).
Generator (TQG) Status LEDs
—The LED on the left blinks green during generator start; it is
steady-on green when the AGS circuit is functional and when the generator is running. The LED on
the right is red if there is a generator fault, solid green when the generator is running, and blinking
green when the generator is starting. (For an AMMPS generator, these LEDs are active but do not
report the status of the generator.)
Auto Generator Start (AGS) Alarm ON/OFF Switch
—In the ON position, an alarm will sound
as warning that the generator has initiated the auto-start protocol and is about to start. The OFF
position disables the alarm for silent operations.
Auto Generator Start (AGS) Test Button
—The Test Button is a push-button momentary switch that
allows the AGS system to be tested for correct wiring and generator start/stop operation.
USB 5 A Breaker
—Push to reset the breaker if the USB port is not operating while the PRO-Verter
is turned on.
PRO-Verter 5000-120 Faceplate
LCD User Interface:
PRO-Verter Control and System
Status
TQG Start/Stop (AGS)Controller
Generator Status LEDs and
AGS Test Button
Auto Generator Start Alarm
ON/OFF Switch
Remote Monitoring Kit
Connection Ports and Cables
Breaker
AC IN
50 A
Breaker
AC OUT
30 A
Breaker
USB
5 A
Breaker
DC OUT
5 A
24 VDC
OUT
5 A
Breaker
AC OUT
20 A
System
Recovery
Switch
AMMPS
RMK (AGS)
COMM Port
Breaker
FANS
1 A
USB Charging Ports (x2)
RMK
Mounting
Location
Specifications
AC Input Reverse Polarity
Indicator LED