|
65
December 2020
|
Solar Stik
®
, Inc.
SYSTEM SETUP AND OPERATION GUIDE FOR THE SOLAR STIK USAF G-BOSS MEDIUM AND HEAVY HYBRID POWER SYSTEM
PRELIMINARY DRAFT
For these AGS faults, refer to the
Solution
immediately following
Fault Test
The generator failed to autostart and run after the red TEST button is pressed on the AGS controller.
Note:
The LCD User Interface can be set to manually turn the generator on and off, which can be
used to test the generator wiring to the AGS.
Fault VDC
The generator failed to autostart and run per the FAVS: F5 Gen Run VDC menu’s start parameters
(24.6 VDC).
Solution
Disconnect the Generator from the System and start it using the generator native controls.
If the generator does not start, check the generator for fault codes, adequate fuel and refer to the
generator Operator and Maintenance Manual.
If the generator starts, reconnect it to the System and attempt to start it manually (“ON”) using the
PRO-Verter control (CTRL 03).
If the generator does not start using the PRO-Verter controls, ensure proper electrical connections
between the PRO-Verter and the generator and refer to the PRO-Verter Operator Manual.
Note:
One of the fault messages above may display on the LCD User Interface when:
• The AGS attempts to start the generator four (4) times, but the generator failed to start and
run per the specific autostart parameters; or
• The generator started, but did not provide the correct Gen Run sense signal to the AGS
controller.