Art.-Nr. 908.30.62.00
Stand 11/2015
- 23 -
3
T e c h n i c a l D a t a
3.1
General
Designation/type
FRIWA 30
Nominal output at 10-45/65°C (CW-HW/HF)
85 kW
Tapping capacity at nominal output
35 l/min
NL number at nominal output
7.5
Output at 10-60/75°C (CW-HW/HF)
90 kW
Tapping capacity at 10-60/75°C
26 l/min
Capacity at 10-60/75°C, mixed to 45°C HW
90 kW
Tapping capacity at 10-60/75°C, mixed to 45°C HW
37 l/min
Max. operating
pressure
Heating side
Service water side
3 bar
10 bar
Max. operating
temperature
Heating side
Service water side
95 °C
65 °C
Connections
Heating side
Service water side
Rp ¾
Rp ¾
Pressure loss on the service water side at nominal output
0.6 bar
Max. pressure loss for piping on the heating side
50 mbar
Circulation pump
Power consumption
Wilo Yonos Para 15/7.0 PWM2
3-45 W
Electrical connection (mains control)
230 V AC/ 50-60 Hz
Materials
Housing/connecting components
CW617N (2.0402)
Plate heat exchanger
Stainless steel, Cu soldered
Seals
AFM
Insulation
EPP foam 0.038 W/mK
3.2
Dimensions/required space
Dimensions and minimum space required for
assembly and maintenance work
Summary of Contents for FRIWA 30
Page 2: ...Deutsch...
Page 19: ...English...