Refer to the Maintenance section for recommendations on cleaning.
Water treatment measures to prevent scale formation (water softening)
Fresh water station with 50 °C hot
water outlet temperature and
Mass concentration of calcium carbonate [mmol/l]
flow < 65 °C
flow > 65 °C
< 1,5 mmol/l (< 150 mg/l)
< 8,4°dH (
≙
14,95°fH)
None
None
1,5 bis 2,5 mmol/l (150 mg/l up to 250 mg/l)
8,4°dH up to 14°dH (
≙
14,95°fH up to 24,92°fH)
None
Recommended
> 2,5 mmol/l (>250 mg/l)
> 14°dH (
≙
24,92°fH)
Recommended
Recommended
It should be noted that decalcification by means of ion exchange does not reduce the con-
ductivity. For this reason, use a full stainless steel exchanger from 500 µS/cm. It can roughly
be calculated that 14° dH corr
esponds to a conductivity of 14° dH * 35 = 490 μS/
cm. Thus,
as a precaution, a full stainless steel exchanger must be used. In addition, fresh water
stations must be grounded so that no current flow over the plate heat exchanger or the piping
is performed.
4
A s s e m b l y
4.1 Wall-mounted assembly
Mark the drilling dimensions as per the draw-
ing and drill with
10 mm.
Insert the rawl plugs.
Tighten the two top screws.
Tighten to a clearance of 3 mm between the
screw head and the wall.