182
Kaco
Procedure
1. Open the inverter as shown in the inverter's instructions.
2. Connect the data cable to the free terminals A and B of inverter 1.
3. Insert the other end of the cable into terminals A and B of inverter 2.
4. Connect the other inverters to each other in the same way.
5. Terminate the last inverter.
Connect the free terminal A to terminal B using the supplied 330
Ω
terminating resistor.
6. Close inverters.
Allocate communication address
•
Recommendation: Continuous numbering starting with 1.
•
Setting: Using the DIP switch inside the inverter.
•
Procedure: Start according to the inverter's instructions
Note
A maximum of 32 inverters can be connected per RS485 bus.