88.1
SolarMax – S, MT, P, TS, TS-SV and HT- series
Termination
Addressing
Interface
No
Yes
RS485
Note regarding the HT series:
Inverter models that have more than 3 MPP trackers are subdivided by the Solar-Log™ into multiple
“virtual” devices. Thus, for inverter type 32HT4, for example, with 4 MPP trackers, two virtual devices
are detected.
►
The reason for this is because the Solar-Log™ is limited to a maximum of 3 MPP trackers per inver-
ter.
Note for Solar-Log
200
The Solar-Log
200
is designed for one inverter only. For this reason, Solar Max inverters of the HT series
with more than 3 MPP trackers cannot be installed to the Solar-Log200 since the
Solar-Log™ subdivides this model of inverter into multiple “virtual” devices.
Overview
•
Integrated interface
•
Where to connect: RJ45 socket on the outside of the inverter
•
Where to connect HT series: RJ45 socket inside the inverter
•
2-pin wiring
•
Communication address must be allocated.
•
Installation steps
•
Switch off the inverters and Solar-Log™
•
Connect inverters to the Solar-Log™
•
Connect the inverters to each other
•
Allocate communication address
Connect inverters to the Solar-Log™
The wiring is done using a
•
ready-made data cable (optional extra; not supplied)
or
•
self-made RS485 data cable with RJ45 plug and terminal block connector.
Summary of Contents for Solar-Log
Page 1: ...1 Components Connection Manual V 4 2 3 Solar Log EN ...
Page 20: ...20 01 Inverter ...
Page 398: ...398 Appendix 113Appendix 113 1 SMA mixed wiring Fig SMA mixed wiring ...
Page 402: ...402 02 Meter ...
Page 444: ...444 03 Battery Systems ...
Page 456: ...456 sonnen Note Only one battery system can be connected to a Solar Log device ...
Page 463: ...463 04 Heating rods ...
Page 470: ...470 05 Heating pumps ...
Page 478: ...478 06 Sensors ...
Page 488: ...488 07 Pyranometer ...
Page 495: ...495 08 Smart Plug components ...
Page 502: ...502 09 Power Charging Stations ...