330
SolaX Power
89.2
SolaX Power X3
Termination
Addressing
Interface
Yes
Yes
RS485
The following types are to be connected according to this diagram:
•
ZDNY-TL10000, ZDNY-TL12000, ZDNY-TL15000, ZDNY-TL17000
Select SolaXPower X3 during the inverter detection.
Overview
•
Integrated interface.
•
2 RJ45 sockets on the outside of the inverter.
•
2-pin wiring.
•
Communication address must be allocated.
•
Installation steps
•
Switch off the inverters and Solar-Log™.
•
Connect inverters to the Solar-Log™.
•
Connect the inverters to each other
•
Allocate communication address.
Address range 1 to 247
Settings on the inverter's display according to the manufacturer's manual.
Connect inverters to the Solar-Log™.
The wiring is done using a
•
self-made, shielded 8 wire data cable and terminal block connector.
•
Where to connect: RJ45 socket on the inverter
Procedure
1. If you make the cable yourself, connect the wires as shown in the following diagram.
Solar-Log™ terminal strip connector
RS485 inverter socket
Terminal
PIN
►
1
►
Pin 4 - Data+
►
4
►
Pin 5 - Data-
2. Insert the RJ45 plug into any RJ45 socket on inverter 1.
3. If no further inverter is connected, terminate the inverter according to the instructions for the inverter.
4. Insert the terminal block connector into the Solar-Log™ RS485 socket.
Summary of Contents for Solar-Log
Page 1: ...1 Components Connection Manual V 4 2 3 Solar Log EN ...
Page 20: ...20 01 Inverter ...
Page 398: ...398 Appendix 113Appendix 113 1 SMA mixed wiring Fig SMA mixed wiring ...
Page 402: ...402 02 Meter ...
Page 444: ...444 03 Battery Systems ...
Page 456: ...456 sonnen Note Only one battery system can be connected to a Solar Log device ...
Page 463: ...463 04 Heating rods ...
Page 470: ...470 05 Heating pumps ...
Page 478: ...478 06 Sensors ...
Page 488: ...488 07 Pyranometer ...
Page 495: ...495 08 Smart Plug components ...
Page 502: ...502 09 Power Charging Stations ...