345
Solutronic
Connect the inverters to each other
•
Connection in the master-slave data network using an 1:1 cable with M12 plug connector (available as an
optional extra from Solutronic).
•
Sockets X6 and X7 are connected to each other electrically.
•
Where to connect: Round pin plug on the outside of the inverter.
Procedure
1. Insert the plug into the X6 socket on inverter 1.
2. Insert the other end of the wire into the X7 socket on inverter 2.
3. Connect the other inverters to each other in the same way.
4. Terminate the last inverter according to the manufacturer's instructions.
Allocate communication address
•
Setting: Using the inverter's control panel, parameter 89 in the communication menu.
Recommendation: Continuous numbering starting with 1.
Set this in the SSP address menu item.
•
Procedure: Start according to the inverter's instructions.
Note
The mode Fixed cos Phi has to be set according to the manufacturer's specifications for all of the inver-
ters to use active and reactive power management.
Summary of Contents for Solar-Log
Page 1: ...1 Components Connection Manual V 4 2 3 Solar Log EN ...
Page 20: ...20 01 Inverter ...
Page 398: ...398 Appendix 113Appendix 113 1 SMA mixed wiring Fig SMA mixed wiring ...
Page 402: ...402 02 Meter ...
Page 444: ...444 03 Battery Systems ...
Page 456: ...456 sonnen Note Only one battery system can be connected to a Solar Log device ...
Page 463: ...463 04 Heating rods ...
Page 470: ...470 05 Heating pumps ...
Page 478: ...478 06 Sensors ...
Page 488: ...488 07 Pyranometer ...
Page 495: ...495 08 Smart Plug components ...
Page 502: ...502 09 Power Charging Stations ...