369
TBEA
100
TBEA
100.1
TBEA
Termination
Addressing
Interface
120
Ω
resistor
Yes
RS485
Supported models (as of firmware 4.2.0):
•
TS50KTL-S
Overview
•
Integrated interface
•
Where to connect: Round sockets on the outside of the inverter.
•
2-pin wiring
•
The communication address has to be assigned.
•
Installation steps
•
Switch off the inverters and Solar-Log™
•
Connect inverters to the Solar-Log™
•
Connect the inverters to each other
•
Assign the communication address; address range 1 to 247
Connect inverters to the Solar-Log™
•
self-made, shielded 2 wire data cable with round plug and terminal block connector.
Procedure
1. If you are fabricating the cable yourself, connect the wires as shown in the following diagram.
Solar-Log™ terminal strip connector
Inverter
Terminal
PIN
►
1
►
A1 or A2
►
4
►
B1 or B2
2. Insert the round plug into the COM round socket 1 on the inverter.
3. If no further inverter is connected, terminate the inverter according to the instructions for the inverter.
4. Insert the terminal block connector into the Solar-Log™ RS485 socket.
Connect the inverters to each other
•
Connect using a data cable with a round plug
•
Where to connect: Round sockets on the outside of the inverter.
Summary of Contents for Solar-Log
Page 1: ...1 Components Connection Manual V 4 2 3 Solar Log EN ...
Page 20: ...20 01 Inverter ...
Page 398: ...398 Appendix 113Appendix 113 1 SMA mixed wiring Fig SMA mixed wiring ...
Page 402: ...402 02 Meter ...
Page 444: ...444 03 Battery Systems ...
Page 456: ...456 sonnen Note Only one battery system can be connected to a Solar Log device ...
Page 463: ...463 04 Heating rods ...
Page 470: ...470 05 Heating pumps ...
Page 478: ...478 06 Sensors ...
Page 488: ...488 07 Pyranometer ...
Page 495: ...495 08 Smart Plug components ...
Page 502: ...502 09 Power Charging Stations ...