421
Inepro
Cable connection via S0:
Solar-Log™ S
0
terminal block
Inepro 1250D
Pin assignment
Pin assignment
1 - S0+
9 - S0+
2 - S0-
8 - S0-
3
4
Place a cable bridge between pin 3 and 4 on the Solar-Log™.
Possible meter operating modes for the Inepro 1250D meter via S0:
•
Total plant meter
•
Sub-consumption meter
•
Consumption meter
•
Generator
Impulse factor of the meter:
400 p / kWh
5.1.1
Connection diagram for different operating modes
Solar-Log™ Inepro 1250D (RS485 or S0) connection assignments
►
As consumption or sub-consumer meter
Connection to the grid (IN) – connection for appliances
(OUT)
►
As inverter / production meter
Connection for the production (IN) – connection to the
grid (OUT)
Note
The Inepro 1250D cannot be used on the same bus input with RS422 connected inverters.