436
Mikro PowerMeter
9
Mikro PowerMeter
9.1
Mikro PowerMeter DPM680
Auswählbar unter „Mikro:DPM680“
Overview
•
The communication address has to be assigned.
•
3-pin wiring.
•
Installation steps:
•
Switch off the meter and the Solar-Log™.
•
Connect the meter to the Solar-Log™.
Connect the meter to the Solar-Log™.
The wiring is done using a
•
self-made cable connection with a terminal block connector.
Cable connection via RS485:
Solar-Log™ RS485 terminal block
Solar-Log 50
Mikro PowerMeter DPM680
Pin assignment
Pin assignment
►
1
1 or 5
►
+
►
3
4 or 6
►
GND
►
4
►
-
Note
The default RS485 communication parameters for the meter are:
Baud: 38400
Data bits: 8
Parity: None
Stop bits: 1
The Solar-Log™ can only communicate with the meter when it has these settings. It is important to
check the settings before performing the device detection.
►
Assign the communication address (according to the manufacturer‘s manual).
►
The settings are adjusted via the device‘s display. (Please refer to the notes and instructions in the
manufacture‘s manual for instructions.)
Summary of Contents for Solar-Log
Page 1: ...1 Components Connection Manual V 4 2 3 Solar Log EN ...
Page 20: ...20 01 Inverter ...
Page 398: ...398 Appendix 113Appendix 113 1 SMA mixed wiring Fig SMA mixed wiring ...
Page 402: ...402 02 Meter ...
Page 444: ...444 03 Battery Systems ...
Page 456: ...456 sonnen Note Only one battery system can be connected to a Solar Log device ...
Page 463: ...463 04 Heating rods ...
Page 470: ...470 05 Heating pumps ...
Page 478: ...478 06 Sensors ...
Page 488: ...488 07 Pyranometer ...
Page 495: ...495 08 Smart Plug components ...
Page 502: ...502 09 Power Charging Stations ...