24
UPS for 208 Vac Grid, B120US Installation Guide, doc. rel. 3.0
Table 3: Recommended clearances
R
ECOMMENDED MINIMUM CLEARANCE AROUND THE
UPS
Front
110 cm (43 in.) Minimum adequate clearance for user access and service.
Rear
100 cm (39 in.) Minimum adequate clearance for cable connections.
Sides
--
No minimum clearance, provided that the UPS is not placed next
to heat-emitting or electronic equipment. If the UPS is placed
next to heat-emitting or electronic equipment, leave at least
20 cm free space between the UPS and the other equipment. The
object here is to avoid subjecting the UPS to additional heat and
to protect the UPS from stray electronic signals.
Figure 8: Recommended clearances around the UPS
3.3.3.
Electrical Site Preparation
Perform the following procedures before connecting any external cables to the UPS.
To perform electrical site preparation:
1.
5 (Circuit Breaker Selectivity – in this Installation Guide.
The chapter includes considerations regarding the size of the external circuit breakers on the
rectifier input and bypass input lines.
2.
Verify that circuit breakers on the electrical panel that supplies the UPS are compliant
with local and national codes and Gamatronic system specifications.