191
UPS for 480 Vac Grid, User Guide, doc. rel.4.0
Register
Variable name
GET Values
Remarks
282
4x0282
Active Alarms Count
Active alarms, except for the ones marked
"ignored" or "for log only" in the controller
configuration
301
4x0301
General Fault
0: Alarm off
1: Alarm on
Any active alarm exists, except for the ones
marked "ignored" or "for log only" in the
controller configuration
302
4x0302
Module 1 Alarm
0: Alarm off
1: Alarm on
303
4x0303
Module 2 Alarm
0: Alarm off
1: Alarm on
304
4x0304
Module 3 Alarm
0: Alarm off
1: Alarm on
305
4x0305
Module 4 Alarm
0: Alarm off
1: Alarm on
306
4x0306
Module 5 Alarm
0: Alarm off
1: Alarm on
307
4x0307
Module 6 Alarm
0: Alarm off
1: Alarm on
308
4x0308
Module 7 Alarm
0: Alarm off
1: Alarm on
309
4x0309
Module 8 Alarm
0: Alarm off
1: Alarm on
310
4x0310
Module 9 Alarm
0: Alarm off
1: Alarm on
311
4x0311
Module 10 Alarm
0: Alarm off
1: Alarm on
312-
318
4x0312- 4x0317 Registers 312 through
318
not relevant for UPS
319
4x0319
Module 18 Alarm
0: Alarm off
1: Alarm on
Only for Mega modular UPS in 20 module
configuration
320
4x0320
Module 19 Alarm
0: Alarm off
1: Alarm on
Only for Mega modular UPS in 20 module
configuration
321
4x0321
Module 20 Alarm
0: Alarm off
1: Alarm on
Only for Mega modular UPS in 20 module
configuration
322
4x0322
Alarm In More Than One
Module
0: Alarm off
1: Alarm on
323
4x0323
Static Switch Warning Or
Alarm
0: Alarm off
1: Alarm on
324
4x0324
Static Switch Warning Or
Alarm
0: Alarm off
1: Alarm on
325
4x0325
Over Temperature
0: Alarm off
1: Alarm on