UPS for 480 Vac Grid, User Guide, doc. rel. 4.0
192
Register
Variable name
GET Values
Remarks
326
4x0326
No AC Output To Load 0: Alarm off
1: Alarm on
327
4x0327
DC Voltage High
0: Alarm off
1: Alarm on
328
4x0328
DC Voltage Low
0: Alarm off
1: Alarm on
329
4x0329
End Of Battery Backup
0: Alarm off
1: Alarm on
330
4x0330
Low Battery Voltage
0: Alarm off
1: Alarm on
331
4x0331
Emergency Power Off Is
Active
0: Alarm off
1: Alarm on
332
4x0332
Batteries Failed Last Test 0: Alarm off
1: Alarm on
333
4x0333
AC Input Voltage Low
0: Alarm off
1: Alarm on
334
4x0334
AC Input Voltage High
0: Alarm off
1: Alarm on
335
4x0335
AC Input Failure
0: Alarm off
1: Alarm on
336
4x0336
No Output Current On
Modules
0: Alarm off
1: Alarm on
337
4x0337
Overload
0: Alarm off
1: Alarm on
338
4x0338
Battery Test In Progress 0: Alarm off
1: Alarm on
339
4x0339
Auxiliary Input Volt-Free
Contact 1 Fault
0: Alarm off
1: Alarm on
340
4x0340
Auxiliary Input Volt-Free
Contact 2 Fault
0: Alarm off
1: Alarm on
341
4x0341
Auxiliary Input Volt-Free
Contact 3 Fault
0: Alarm off
1: Alarm on
342
4x0342
Auxiliary Input Volt-Free
Contact 4 Fault
0: Alarm off
1: Alarm on
343
4x0343
Auxiliary Input Volt-Free
Contact 5 Fault
0: Alarm off
1: Alarm on
344
4x0344
Shutdown By Off Button
on Touch Panel
0: Alarm off
1: Alarm on
345
4x0345
Shutdown By Hardware
Off Button
0: Alarm off
1: Alarm on
346
4x0346
Shutdown Through
Communication
0: Alarm off
1: Alarm on
347
4x0347
Shutdown Due To End Of
Backup
0: Alarm off
1: Alarm on