42
UPS for 400 Vac Grid, Installation Guide, doc. rel. 3.0
3.3.6.2.
Continuing first time startup process
To continue the first time startup process:
1.
If you are using lithium-ion batteries, contact Gamatronic support for configuration
instructions and check the values in the
Setup > Battery
parameters against the
information in the battery manufacturer’s data sheet. Verify that the parameter values
are appropriate for the batteries you have chosen.
2.
Turn off the bypass and rectifier input circuit breaker.
Figure 19: Flat cables
3.
Insert a single power module and connect the right and left flat cables. If the bypass
and input are bridged, slide out the Static Switch at least 5 inches.
Figure 20: Static switch
4.
If the bypass and input are bridged, slide out the Static Switch (see Figure 20 above) at
least 5 inches.
5.
Turn on the rectifier input circuit breaker, wait for the power module to be fully
operational (i.e., both LED indicators are green).