44
UPS for 400 Vac Grid, Installation Guide, doc. rel. 3.0
8.
Select
Complete Shutdown
.
The selected power module is shutdown.
9.
Insert the next power module 3/4 of the way in and attach the 2 flat cables then, slide it
in fully.
10.
Turn on the power module (
Main > Operation > Turn On/Off > Modules on
).
The Modules on screen appears:
Figure 23: Modules On screen
11.
Select only the newly added power module.
The power module becomes highlighted.
12.
Select
Confirm
.
13.
The selected power module is switched on.
Notice that the active power module is highlighted in blue and is active (module #2), while the
primary power module is in Standby State (module #1) because it was shutdown.
14.
Once fully operational, fully shutdown the power module just added and insert the next
power module.
15.
Repeat this process for each additional power module during first time installation.
16.
After each module has been individually powered up and shutdown perform a
complete system shutdown (
Main > Operation > Turn On/Off > System off
).
The
Confirm Turning the System Off
screen appears: