UPS for 400 Vac Grid, Installation Guide, doc. rel. 3.0
61
The system will run on ECO mode until either there is a variant in the grid power
supply or the system is manually transferred back to normal mode.
You have successfully enabled ECO Mode and turned ECO Mode on.
3.4.6.
Test: IP Communication with Controller
This test is designed to verify that the System Controller is properly configured for remote
monitoring. Verifying communication and that the Web server built into the System Controller is
functioning properly.
If you do not intend to use remote monitoring of the UPS at this time you can skip
this test.
The following procedure is provided in general terms. Specifics will vary depending on the
operating system of the computer you are using.
To test IP communication with the controller:
11.
Use an RJ45-to-RJ45 straight or crossed cable to attach a PC or laptop or other external
computer to the Ethernet (RJ45) port on the UPS’s system controller.
12.
Configure the network connections of the external computer so that the computer is in
the same domain as the UPS
–
that is, so that the first three nodes of the computer’s IP
address match the first three nodes of the UPS’s IP address.
For example, if the UPS’s IP address is “192.212.118.100”, define your computer’s IP address as
“192.212.118.xxx”, where “xxx” is a number other than “100” in this case.
13.
Define the subnet mask of your computer as “255.255.255.0”.
14.
Open a browser on the external computer and enter the IP address of the UPS’s system
controller in the browser’s address field to verify that yo
u can reach the Web server on
the system controller.