49
L30US-IB80, L30US-IB00, L40US UPS
4.3.7.5.
Dry contact setup
Battery Abnormal BCB trip (DRV):
Enable or disable BCB trip single output. The default
value is Disable.
Bypass Feedback Trip:
Enable or disable bypass feedback output. The default value is
Disable.
External Maint. Breaker (MT):
Enable or disable external maintenance breaker connection
detection. The default value is Disable.
Battery breaker (BAT):
Enable or disable battery breaker connection detection. The default
value is Disable.
NOTE!
Each dry contact can be N.O or N.C.