63
L30US-IB80, L30US-IB00, L40US UPS
5.
Appendix 1: Specifications
Table 10 Specifications
Model
L30US-
IB80
L30US-IB00
L40US
General
Capacity (VA/Watts)
30K / 30K
40K / 40K
Input and output type
4W/4W+PE
Design rating (power module
technical rating)
30KW power module x1
20KW power
module x2
Efficiency
(with linear
load)
Normal mode
Up to 94%
ECO mode
Up to 98%
Short circuit capacity Icc (KAIC)
5
Parallel system (integrated
parallel / Static Switch Cubicle)
Up to 2
Configuration
s or
architecture
Standalone Yes
Parallel Yes
Frequency
converter
Yes
Bus Synchronization
without external box
No
Input
THDI (100% Load)
<3%
PF (100% R Load)
>0.99
Frequency tolerance
40-70Hz