Appendix B: Specifications
SolarEdge Installation Guide - MAN-01-00060-2.6
64
Three Phase inverters
SE4k
SE5k
SE7k
SE8k
SE9k
SE10k
SE12.5k SE15k
SE16k
SE17k
Unit
Exit
AC output power rating
4000
5000
7000
8000
9000
10000
12500
15000
16000
17000
GOES
Maximum output power AC
4000
5000
7000
8000
9000
10000
12500
15000
16000
17000
GOES
Rated output voltage CA -
line by line / line to neutral
(nominal)
380/220; 400/230; 415/240
Vac
AC output voltage range
184 to 264.5
Vac
AC frequency
(nominal)
50/60 ± 5
Hz
maximum intensity DC
output (per phase)
6.5
8
11.5
13
14.5
16
20
23
25.5
26
AT
Protection against
maximum current of the
overcurrent
6.5
8
11.5
13
14.5
16
20
23
25.5
26
AT
residual current detector /
detector gradual residual
current
300/30
my
Supported networks -
three phase
3 / N / PE; 230/400
CA startup current
(peak / duration)
154/0050
A / ms
maximum fault current
output
33
40
AT
power factor range
+ / - 0.9 to 1.0
Protection class
class I
Utility Monitoring, islanding
protection, power factor
configurable, configurable
thresholds countries
Yes
category
protection against
overvoltage
III