Connecting to the Grid and to Backed-up Loads
This section describes:
l
Connection to the AC Grid.
l
Connection between the inverter to the backed-up loads panel.
NOTE
Each inverter should be connected to a separate backup panel. Do not share backup output between
inverters.
Figure 22: Connection to grid, backed-up loads
Prepare cables and connect as described in the following table:
Recommended cable type
(min-max AWG)
StorEdge Connection
Unit connection
External connection
Grid
6 AWG (4-20 AWG)
3-pin terminal block: Grid L1
Main distribution panel: L1
3-pin terminal block: Grid L2
Main distribution panel: L2
3-pin terminal block: Grid N
Main distribution panel: N
Min. 10 AWG grounding wire
to ground
Backed-up loads panel
6 AWG (4-20 AWG)
3-pin terminal block: L1
Backed-up loads panel: L1
3-pin terminal block: L2
Backed-up loads panel: L2
3-pin terminal block: N
Backed-up loads panel: N
Min. 10 AWG grounding wire
to ground
SolarEdge
-
StorEdge Installation Guide MAN-01-00262-1.0
36
Connecting to the Grid and to Backed-up Loads