l
##
: The total number of slaves detected on the specific port
l
Dev
: The type of device that was configured to a specific port (based on the port’s functionality), as
follows:
o
SE
: SolarEdge device (default)
o
DM
: Revenue meter
o
LGR
: Non-SolarEdge logger
l
PROT
: The protocol type to which the port is set:
o
For a SolarEdge device:
n
S
: SolarEdge slave
n
M
: SolarEdge master
n
P2P
: ZigBee point-to-point
n
MPM
: ZigBee multipoint master (for the SolarEdge ZigBee home gateway)
n
MPS
: ZigBee multipoint slave (for a ZigBee router module)
o
For electricity meters, refer to the
application note - Connecting an Electricity Meter to SolarEdge
Devices
at
http://www.solaredge.us/files/pdfs/connecting-revenue-grade-meter-to-solaredge-
devices.pdf
.
o
SS
: SunSpec - for a non-SolarEdge logger (monitoring and control)
Smart Energy Management Status
This screen is displayed only when Smart Energy Management is enabled. The screen shows energy details
of the site:
S i t e L i m i t :
7 . 0 k W
S i t e P r o d :
1 0 . 0 k W
S i t e E x p o r t :
4 . 0 k W
S e l f - c o n s u m e :
6 . 0 k W
l
Site Limit
: The limit that was defined for the site
l
Site Prod
: The power produced by the site
l
Site Feed
: The power that is fed into the grid
l
Self-consume
: The PV power consumed by the site
Power Control Status
This screen is displayed only when Power Control is enabled (available from communication board (CPU)
firmware version 2.7xx/3.7xx and later).
P W R C T R L :
R E M O T E
P W R L i m i t : 1 0 . 0 4 k W
C o s P h i :
0 . 9
P o w e r P r o d :
7 0 0 0 W
l
PWR CTRL
: The power control status:
o
REMOTE
- Communication with the RRCR or smart energy manager is confirmed/validated.
o
LOCAL
- The power is controlled locally (e.g. by a fixed limit), or this inverter limits the PV power
production to its relative portion of the feed-in power limit, as a result of disconnected
communication with the smart energy manager. If this status appears, check the communication
to the smart energy manager or the communication to the meter.
Chapter 7: User Interface
SolarEdge
-
StorEdge Installation Guide MAN-01-00262-1.0
53