Safety and Installation instructions   

© The Solaria Corporation. Contents subject to change without notice. 

Document SPS-1006 Rev 02, April 25, 2017 

 

 

Do not remove or alter the module frame. Creating additional mounting 
holes may damage the module and reduce the strength of the frame.  

 

The Solaria modules must be mounted using industry standard ground 
mount hardware roof mount hardware, or single and dual axis PV 
trackers. 

If other

 

mounting means are employed, then product 

certification or fire class ratings may be affected. 

 

For roof mounting, the modules should be mounted over a fire-resistant 
covering rated for the application. 

 

Clearance of 7 mm or more between modules is required to allow for 
thermal expansion of the frames. 

 

Clearance of 100 mm or more is recommended between the modules and 
the rooftop or nearest surface. 

 

Always keep the back surface of the module free from any foreign objects 
or structural elements which could come into contact with the module. 

 

Ensure that the modules are not subject to wind or snow loads in excess 
of the maximum permissible loads and are not subject to excessive 
forces due to thermal expansion of the support structure. 

 

Modules have been tested to Mechanical Loading Test requirements of 
UL1703. 

 

The fire rating of this module is valid only when mounted in the manner 
specified in the mechanical

 

mounting instructions. 

 

The module is considered to be in compliance with UL1703 only when the 
module is mounted in the manner specified by the mounting instructions. 

 

A module with exposed conductive parts is considered to be in 
compliance with UL1703 only when it is electrically grounded in 
accordance with the instructions presented in this document and the 
requirements of the National Electrical Code. 

 

Any module without a frame (laminate) shall not be considered to comply 
with the requirements of UL1703 unless the module is mounted with 
hardware that has been tested and evaluated with the module under this 
standard or by a field inspection certifying that the installed module 
complies with the requirements of UL1703. 
 
 
 

Summary of Contents for PowerXT-R

Page 1: ...tion instructions The Solaria Corporation Contents subject to change without notice Document SPS 1006 Rev 02 April 25 2017 SAFETY INSTALLATION AND OPERATIONS MANUAL FOR US INSTALLATIONS Solaria PowerX...

Page 2: ...details may be found at www solaria com 2 0 Safety Precautions Before installing the modules read all safety instructions in this document Modules produce direct current DC when exposed to light Direc...

Page 3: ...stallation and inspection requirements Module support structures should be wind rated per local code and approved for use by the local authorities 2 1 FIRE RATING AND SAFETY Solaria PowerXTTM resident...

Page 4: ...o combining with other strings The maximum fuse size allowed is noted on the module label Connection cables and wiring shall be supported with plastic or rubber cable ties and clips to the module supp...

Page 5: ...rly rated and certified over current device must be connected in series with each module or string of modules when reverse currents can exceed the value of the maximum protective fused value noted on...

Page 6: ...plit ring lock washers flat washers and the like are used to attach the solar module to a listed grounding bonding device the attachment must be made in conformance with the grounding device manufactu...

Page 7: ...mechanical bond between the tooth lock washer and the frame of the module will ensure a good electrical bonding path The 10 32 assembly attachment screw must be tightened between 20 25 inch pound A 1...

Page 8: ...eet the following requirements For most installations including rooftop and tracker installations modules should be secured with bolts or PV module specific clamps at the four outermost 7 mm mounting...

Page 9: ...ould come into contact with the module Ensure that the modules are not subject to wind or snow loads in excess of the maximum permissible loads and are not subject to excessive forces due to thermal e...

Page 10: ...the axis is not aligned with the North South direction it is critical that the controller of the tracker corrects for this misalignment 5 0 Maintenance Solaria modules are virtually maintenance free...

Page 11: ...nance of the module The Solaria Corporation assumes no responsibility for any infringement of patents or other rights of third parties that may result from the use of the module No license is granted...

Page 12: ...urrent Isc A 9 49 Voltage at Pmax V 36 6 Current at Pmax A 9 2 Max Series Fuse Rating A 15 UL Max System Voltage V 1000 TEMPERATURE SPECIFICATIONS Coefficient of Power 0 40 C Coefficient of Voltage 0...

Page 13: ...structions The Solaria Corporation Contents subject to change without notice Document SPS 1006 Rev 02 April 25 2017 8 0 Mechanical Dimensions Module Weight 20 1 kg 44 31 lbs Nominal dimensions in mill...

Page 14: ...nstructions The Solaria Corporation Contents subject to change without notice Document SPS 1006 Rev 02 April 25 2017 Solaria USA 6200 Paseo Padre Pkwy Fremont CA 94555 United States of America T 1 510...

Reviews: