Alarm
Troubleshooting measures
PV over voltage
■
Check the number of PV modules and adjust it if need.
PV under voltage
■
When sunlight intensity weakens, PV modules voltage
decreases. No action is needed.
■
If such phenomena occur when sunlight intensity does not
weaken, check if there is short circuit, open circuit etc. in
the PV strings.
Insulation resistance
abnormal
■
Check the insulation resistance against the ground for the
PV strings. If a short circuit has occurred, rectify the fault.
■
If the insulation resistance against the ground is less than
the default value in a rainy environment, set Insulation
resistance protection on SE Touch.
Residual current abnormal
■
1. If the alarm occurs accidentally, possibly the external
circuits are abnormal accidentally. The inverter automati-
cally recovers to the normal operating status after the fault
is rectified.
■
2. If the alarm occurs repeatedly or lasts a long time, check
whether the insulation resistance against the ground of PC
strings is too low.
PV strings abnormal
■
Check whether the PV string is shielded.
■
If the PV string is clean and not shielded, check whether the
PV modules are aging or deteriorated.
PV strings reverse
■
Check whether the cables of PV strings are correctly con-
nected. If they are connected reversely, reconnect the
cables.
BUS under voltage
BUS over voltage
Inverter module fault
Boost circuit abnormal
■
If the alarm occurs occasionally, the inverter can automati-
cally recover to the normal operating status after the fault is
rectified.
■
If the alarm occurs repeatedly, contact your dealer for tech-
nical support.
EEPROM fault
■
Replace the monitoring board
Zero power and yellow alarm
light illuminating in remote
monitoring system
■
If modem or other data logger is used, please reboot it; if it
still does not work after rebooting, contact your dealer.
remote monitor displays zero
power generation
■
If modem or other data logger is used, please reboot it; if it
still does not work after rebooting, contact your dealer.
remote monitor displays no
output voltage
■
Check if DC switch is damaged, and if not, switch it to ON.
If it still doesn’t work, contact your dealer.
Inverter off grid
■
Wait till power is restored;
■
Turn DC switch to ON, and if DC switch trips a lot contact
your dealer. .