ALARM
TYPE
SOLUTION
E014
Low grid voltage
■
Make sure that the mains voltage is within the range allowed
by local regulations.
■
Check the network impedance.
■
If the mains voltage is not within the permitted range for
reasons due to the local grid conditions, contact the grid
operator to evaluate the possibility of adapting the voltages
at the connection point or request approval for the change to
the operating limits.
■
If the mains voltage is within the allowed range, but the
alarm persists, contact the technical support service.
E015
High grid frequency
■
Make sure that the grid frequency is within the range
allowed by local regulations.
■
If the grid frequency is not within the permitted range for
reasons due to the local grid conditions, contact the grid
operator to request approval for the change to the operating
limits.
■
If the grid frequency is within the allowed range, but the
alarm persists, contact the technical support service.
E016
High grid frequency
■
Make sure that the grid frequency is within the range
allowed by local regulations.
■
If the grid frequency is not within the permitted range for
reasons due to the local grid conditions, contact the grid
operator to request approval for the change to the operating
limits.
■
If the grid frequency is within the allowed range, but the
alarm persists, contact the technical support service.
E017
High grid frequency
■
Make sure that the grid frequency is within the range
allowed by local regulations.
■
If the grid frequency is not within the permitted range for
reasons due to the local grid conditions, contact the grid
operator to request approval for the change to the operating
limits.
■
If the grid frequency is within the allowed range, but the
alarm persists, contact the technical support service.
E018
Low grid frequency
■
Make sure that the grid frequency is within the range
allowed by local regulations.
■
If the grid frequency is not within the permitted range for
reasons due to the local grid conditions, contact the grid
operator to request approval for the change to the operating
limits.
■
If the grid frequency is within the allowed range, but the
alarm persists, contact the technical support service.
E019
Disconnection from
the gird imposed
by the distribution
network operator.
■
Intervention of the interface device imposed by the network
operator.