76
en
MPP Tracker 2
MPP Tracker 1
MPP Tracker 3
DC+
DC-
DC+
DC-
DC+
DC-
correct connection!
CAUTION
n
Use only connectors from the MC4 series made by MultiContact for connecting the
DC feed lines to the inverter.
n
Due to the transformerless circuit type of the MT series inverters, the plus or minus
pole of the PV generator must not be earthed under any circumstances. Otherwise,
the isolation monitoring in the inverter prevents a mains connection.
n
Select cable cross-sections for the DC feed lines corresponding to your plant configu-
ration and in conformance with the valid local installation regulations.
n
Remember that the shared plus and minus pole of a string must always be con-
nected to the same tracker.
n
The position of the DC disconnector Q1 must be “O” (Off).