NOTE
MaxTalk 2 Pro, the extension to the standard MaxTalk 2 software, allows authorised
skilled workers to individually adjust the operating parameters. The required “MT series
parameter configuration using MaxTalk 2 Pro” instruction manual can be found on our
website www.solarmax.com (Downloads area). You can request MaxTalk 2 Pro from the
SolarMax Service Centre. The contact details can be found overleaf.
Parameter
Description
Unit
Country
Country setting at the time of commissioning
-
Grid
Grid connection selected during initial start-up (low/medium voltage)
-
Plant type
Plant rating selected during initial start-up:
< 13.8kVA, 13.8–30kVA, or > 30kVA / VDE 0126-1-1
-
Vac min 1
Minimum admissible mains voltage (first limit)
V
t Vac min 1
Release time for minimum admissible mains voltage
ms
Vac max 1
Maximum admissible mains voltage (first limit)
V
t Vac max 1
Release time for maximum admissible mains voltage
ms
Vac min 2
Minimum admissible mains voltage (second limit)
V
t Vac min 2
Release time for minimum admissible mains voltage
ms
Vac max 2
Maximum admissible mains voltage (second limit)
V
t Vac max 2
Release time for maximum admissible mains voltage
ms
Vac 10 min max
Maximum admissible average value of the mains voltage over the last
10 minutes
V
f min 1
Minimum admissible mains frequency (first limit)
Hz
t f min 1
Release time for minimum admissible mains frequency
ms
f max 1
Maximum admissible mains frequency (first limit)
Hz
t f max 1
Release time for maximum admissible mains frequency
ms
f min 2
Minimum admissible mains frequency (second limit)
Hz
t f min 2
Release time for minimum admissible mains frequency
ms
f max 2
Maximum admissible mains frequency (second limit)
Hz
t f max 2
Release time for maximum admissible mains frequency
ms
df/dt max
Maximum admissible change of the mains frequency per second
Hz/s
Iac max
Maximum admissible mains current (per shift)
A
Iac mean max
Maximum admissible DC share of the fed-in mains current
A
Pac max
Maximum effective power to be fed
W
S max
Maximum apparent power to be fed.
VA
Island detection
Immediate grid disconnection when island operation detected
Inactive/on