91
Parameter
Description
Unit
Monit. ext. input
The status signalling contact is configured for monitoring an external
input.
Inactive/on
Restart delay
Delay time before grid reconnection upon previous failure-related grid
disconnection.
s
Pac progression
Maximum increase of the effective power during grid reconnection
upon previous failure-related grid disconnection.
%/min
Soft Start
Maximum increase of the effective power at grid connection. This
gradient, if activated, is always effective, as opposed to Pac progres-
sion (even during restart in the morning).
W/s
Mains check
Additional monitoring before connecting to the grid
Inactive/on
- Vac MC max
Maximum admissible mains voltage at mains check
V
- Vac MC min
Minimum admissible mains voltage at mains check
V
- f MC max
Maximum admissible mains frequency at mains check
Hz
- f MC min
Minimum admissible mains frequency at mains check
Hz
- t MC monitoring
Duration of mains check
s
Ierr max
Maximum admissible leakage current (effective value) on the DC end
mA
P(f)-Mode
Frequency-dependent power reduction
Inactive/on
- Reduction
Reduction of effective power Pac in P(f) mode
%/Hz
- f start
Starting frequency of the P (f) mode
Hz
- f stop
Stop frequency of the P(f) mode
Hz
- Re-increase
Maximum increase to the maximum effective power Pac max after the
P(f) mode was exited.
%/min
Q-Mode
Selected reactive power mode: off, cos(
φ
), cos (
φ
)(Pac), Q, or Q(Vac)
-
- Vac Lock
Switch with hysteresis behaviour for the reactive power modes cos(
φ
)
or cos(
φ
)(Pac). When the switch is activated, the selected reactive
power mode is switched on and/or off according to the limit values
Vac Lock-In and Vac Lock-Out.
Inactive/on
- Vac Lock-In
Upper limit value of the mains voltage for Vac Lock. Vac Lock switches
on the selected reactive power mode.
V
- Vac Lock-Out
Lower limit value of the mains voltage for Vac Lock. Vac Lock switches
off the selected reactive power mode (Q mode = off).
V
FRT
Fault ride through function for dynamic grid support
Inactive/on
- K-Factor
Reactive current static factor for voltage support with reactive current
during mains drops
-