103
Warning
Cause
Measure
RTC error
The RTC (real-time clock) in
the inverter is malfunctioning,
the date and time have been
reset.
If this problem happens fre-
quently, contact the SolarMax
Service Centre. Set the time
and date correctly.
Flash error
A flash error has occurred.
Inverter mains operation con-
tinues to be guaranteed.
Contact the SolarMax Service
Centre.
Firmware mismatch
The firmware versions of the
inverter controllers do not
match.
Contact the SolarMax Service
Centre.
10.2.3 Failures
Status message
Cause
Measure
Vdc too high (VDC3, VDC2,
VDC1)
The DC input voltage at the
specified inverter DC connec-
tion is too high.
Switch off the DC discon-
nector Q1 immediately and
disconnect the PV generator
from the inverter. Check
the dimensioning of the PV
generator.
No mains
No mains BP
There is no mains voltage
or the AC supply has been
interrupted.
Check the AC supply.
Mains error
Mains error BP
The grid has been switched
off.
If this problem continues to
occur, contact the responsible
grid operator.
Frequency too high
Frequency too high BP
The mains frequency is
outside of the f max 1 or f max
2 limit values.
Frequency too low
Frequency too low BP
The mains frequency is
outside of the f min 1 or f min
2 limit values.
Vac too high (L1 L2 L3)
Vac too high BP (L1 L2 L3)
The mains voltage at the
specified phase is outside of
the Vac max 1 or Vac max 2
limit values.
Vac too low (L1 L2 L3)
Vac too low BP (L1 L2 L3)
The mains voltage at the
specified phase is outside of
the Vac min 1 or Vac min 2
limit values.