113
Parameter
Unit
Greece
Greece
Portugal
Great
Britain
Switzerland
Bulgaria
Mainland
Islands
- t MC monitoring
s
180
180
20
180
30
30
Island Detection
On/Off
On
On
On
On
On
On
Soft Start
W/s
0
0
0
0
0
0
Pac progression
%/min
0
0
0
0
0
0
P(f)-Mode
On/Off
-
-
-
-
-
-
- f start
Hz
-
-
-
-
-
-
- f stop
Hz
-
-
-
-
-
-
- Reduction
%/Hz
-
-
-
-
-
-
- Re-increase
%/min
-
-
-
-
-
-
Q-Mode
Off
Off
Off
Off
Off
Off
- Vac Lock
On/Off
-
-
-
-
-
-
- Vac Lock-In
V
-
-
-
-
-
-
- Vac Lock-Out
V
-
-
-
-
-
-
FRT
On/Off
-
-
-
-
-
-
- K factor
-
-
-
-
-
-
S max SM8MT2
VA
8000
8000
8000
8000
8000
8000
S max SM10MT2
VA
10000
10000
10000
10000
10000
10000
S max SM13MT2/3
VA
13000
13000
13000
13000
13000
13000
S max SM15MT2/3
VA
15000
15000
15000
15000
15000
15000
Pac max SM8MT2
W
8000
8000
8000
8000
8000
8000
Pac max SM10MT2
W
10000
10000
10000
10000
10000
10000
Pac max SM13MT2/3
W
13000
13000
13000
13000
13000
13000
Pac max SM15MT2/3
W
15000
15000
15000
15000
15000
15000
Iac max SM8MT2
A
12
12
12
12
12
12
Iac max SM10MT2
A
16
16
16
16
16
16
Iac max SM13MT2/3
A
20
20
20
20
20
20
Iac max SM15MT2/3
A
22
22
22
22
22
22
Parameter
Unit
Romania
Hungary
Turkey
China
Israel
Australia
Vac min 1
V
184
184
184
196
207
207
t Vac min 1
ms
200
200
200
2000
2000
2000
Vac max 1
V
264
264
264
253
264
264
t Vac max 1
ms
200
200
200
2000
2000
2000
Vac min 2
V
0
0
0
115
0
0
t Vac min 2
ms
0
0
0
100
0
0
Vac max 2
V
0
0
0
0
0
0
t Vac max 2
ms
0
0
0
0
0
0
Vac 10 min max
V
253
253
253
0
0
0
Monit. ext. input
On/Off
-
-
-
-
-
-
f min 1
Hz
47.5
47.5
47.5
49.5
45.5
45.5
t f min 1
ms
200
200
200
600500
2000
2000
f max 1
Hz
50.2
50.2
50.2
50.2
54.5
54.5
t f max 1
ms
200
200
200
120500
2000
2000
f min 2
Hz
0
0
0
48
0
0
t f min 2
ms
0
0
0
200
0
0
f max 2
Hz
0
0
0
50.5
0
0
t f max 2
ms
0
0
0
200
0
0
df/dt max
Hz/s
0
0
0
0
0
0
Ierr max
mA
300
300
300
300
300
60
Summary of Contents for 10MT2