115
Parameter
Unit
Rest of the world
t f max 1
ms
500
f min 2
Hz
0
t f min 2
ms
0
f max 2
Hz
0
t f max 2
ms
0
df/dt max
Hz/s
0
Ierr max
mA
300
Iac mean max
mA
1000
Restart delay
s
0
Mains check
On/Off On
- Vac MC max
V
264
- Vac MC min
V
196
- f MC max
Hz
51
- f MC min
Hz
47
- t MC monitoring
s
30
Island Detection
On/Off On
Soft Start
W/s
0
Pac progression
%/min 0
P(f)-Mode
On/Off -
- f start
Hz
-
- f stop
Hz
-
- Reduction
%/Hz
-
- Re-increase
%/min -
Q-Mode
Off
- Vac Lock
On/Off -
- Vac Lock-In
V
-
- Vac Lock-Out
V
-
FRT
On/Off -
- K factor
-
S max SM8MT2
VA
8000
S max SM10MT2
VA
10000
S max SM13MT2/3
VA
13000
S max SM15MT2/3
VA
15000
Pac max SM10MT2
W
8000
Pac max SM8MT2
W
10000
Pac max SM13MT2/3
W
13000
Pac max SM15MT2/3
W
15000
Iac max SM8MT2
A
12
Iac max SM10MT2
A
16
Iac max SM13MT2/3
A
20
Iac max SM15MT2/3
A
22
Summary of Contents for 10MT2