22
17/20/22 SHT
25/28/30 SHT
Fig. 15: Route connection for the installation of PV strings
Number of
cable pairs
Number of input route
Inverter type
1
All
All types
2
PV1 and PV4
All types
3
PV1, PV2 and PV4
All types
4
PV1, PV2 and PV4, PV5
All types
5
PV1, PV2, PV3, PV4 and PV5
Only for 25SHT, 28SHT, 30SHT
6
PV1, PV2, PV3, PV4, PV5 and PV6
Only for 25SHT, 28SHT, 30SHT
Connectors of PV string cabels
Ensure that cables of the proper type are being used to connect the inverter to the PV gener-
ator. In particular, PVC and H07RN-F non-tinned cables are NOT recommended.
The PV cables must be terminated with the Amphenol H4 (MC4 compatible) provided with
the inverter.
If different types of connectors are used, or if different installation tools and procedures are
used, then it may not be possible to ensure safety and technical performance.
The 25/28/30 SHT units have integrated 15 A string fuses. The string fuses prevent too high
reverse current.
The following Connectors are recommended for PV strings:
■
Positive pole connector (+), female: Amphenol H4CFC4 S
PC
Insulation layer
Locking nut
Fig. 16: Positive pole female connector