15
3.5
Operating elements at the MCU
The TS-SV Master Control Unit (MCU) is the central control and operating unit (master
stations only).
The interfaces and terminals at the MCU allow many communications and monitoring
options, see Section 14. In addition, the MCU has a mounting rail for the installation of
the MaxWeb xp/NX data logger and the potential equalization set (PAS).
OFF
ON
1
2
No.
Description
1
Graphics display (see Section 7.1)
2
Main switch
Function of the main switch
When the main switch is switched off, the mains contactors of the inverters are opened
and the Compact Station is disconnected from the mains network. The components in
the Compact Station remain charged with high voltage. The Compact Station must be
powered down as described in Section 9 before the inverters are opened.