6.3.1 Configuring the display language and system time
After initial start-up, set the display language and check the system time of the inverter.
In the "Settings" menu, select the following parameters and enter the desired values:
Parameter
Description
Language
Selection of the display language: German, English, French, Italian or
Spanish. he display language selection does not depend on the selected
country.
Time
System time of the inverter.
Date
The date displayed by the inverter
6.3.2 Configuring the network parameters
Device address
A device address must be assigned to the inverter in order to communicate via RS485
interface or Ethernet. Within the MaxComm network, the device address must exist once
only.
1. In the "Settings" menu, select the "Device address" parameter.
2. Set the parameter to the required value:
Parameter
Description
Device address
Address range: 1…249
Configuring the Ethernet interface
In addition to the device address, the following settings must be made to communicate
in a LAN network:
In the "Settings" menu, select the following parameters and enter the required values:
Parameter
Description
IP
Specification of a free IP address within the LAN network.