60
Status message
Cause
Measures
Incorrect rotation dir.
The rotational direction of the
connected mains phases is
wrong.
Connect the mains phases
so that they are connected
clockwise.
Error ext. control
The communication to the
remote control is interrupted.
The time limit between two
control commands was
exceeded.
Once the remote control has
re-established communica-
tion, the Compact Station will
automatically resume mains
operation.
If this occurs repeatedly,
please check the network
connections.
8.2.4 Error
Status LED: red
Status message
Cause
Measures
Device error (+ error code)
An internal error has occurred
in one inverter.
Note the displayed two-digit
error code and contact the
SolarMax Service Center.
8.2.5 Blockings
Status LED: flashes red
Status message
Cause
Measure
Main switch off
The main switch is in the
"OFF" position.
Turn the main switch on.
Shutdown 1
Shutdown 1 (shutdown contact
1) is activated.
Reverse the shutdown / block.
Shutdown 2
Shutdown 2 (shutdown contact
2) is activated.
External blocking
There is a 0% command from
MaxRemote (coming from the
grid operator).
None. Wait until the grid ope-
rator cancels the system block
via MaxRemote.
Program firmware
The system firmware is cur-
rently being updated.
None. The system automati-
cally resumes mains operation
once the firmware update is
complete.
Repeated short-circuit
The MCU has detected several
(>2) short-circuits on the AC
side within a certain period
of time.
Contact your grid operator in
order to eliminate the cause of
the short-circuits.