76
Parameter
Unit
Germany
Spain
Italy
France
Great Britain
- f MC max
Hz
-
-
50.1
-
-
- f MC min
Hz
-
-
49.9
-
-
- MC time
s
0
0
300
0
0
- Reduction
%/Hz
40
40
83
40
40
- Re-increase
%/min
-
10
5
10
10
Q mode
Off
Off
Off
Off
Off
FRT
On/Off
On
On
On
Off
Off
- K factor
2.0
1.0
0.0
0.0
0.0
S max
kVA
738
738
738
738
738
Pac max
kW
738
738
738
738
738
Iac max
A
1332
1332
1332
1332
1332
Parameter
Unit
China
USA
Others
Others 60 Hz
Vac min 1
V
272
281.6
272
281.6
t Vac min 1
ms
2000
2000
1500
2000
Vac max 1
V
352
352
368
352
t Vac max 1
ms
2000
1000
200
1000
Vac min 2
V
160
160
-
160
t Vac min 2
ms
100
160
0
160
Vac max 2
V
-
384
-
384
t Vac max 2
ms
0
160
0
160
Vac 10 min max
V
-
-
-
-
f min 1
Hz
49.5
59.3
47
59.3
t f min 1
ms
600500
2000
500
2000
f max 1
Hz
50.2
60.5
52
60.5
t f max 1
ms
120500
160
500
160
f min 2
Hz
48
57
-
57
t f min 2
ms
200
160
0
160
f max 2
Hz
50.5
-
-
-
t f max 2
ms
200
0
0
0
Restart delay
s
0
0
0
0
Mains check
On/Off
On
On
On
On
- Vac MC max
V
352
339.2
368
339.2
- Vac MC min
V
272
294.4
272
294.4
- f MC max
Hz
50.2
60.5
51
60.5
- f MC min
Hz
49.5
59.3
47
59.3
- t MC monitoring
s
60
300
30
300
Island detection
On/Off
On
On
Off
On
OV Detection
On/Off
On
On
On
On
Soft Start
W/s
1140
-
-
-
Pac progression
%/min
-
-
-
-
P(f) mode
(1/2/3/off)
Off
Off
Off
Off