558 S0 interface
In accordance with DIN EN 62053-31 this interface can be used to connect an energy
counter to the inverter for the purpose of the control self-consumption (see Section 5.5.9).
From experience, SolarMax can recommend the following electronic energy counters:
Berg MCi32WP and Berg B23 311.
The S0 interface is configured with the free MaxTalk 2 Pro service software.
Connection conditions
■
■
Energy counters are only permitted with S0 pulses for feed-in (S0 pulses for both
directions of energy flow are not permitted).
■
■
The pulse rate of the energy meter must be between 1 000 and 10 000 pulses
per kWh.
■
■
Connectable cable diameters: min. 9.5 mm / max. 12.5 mm
■
■
Connectable conductor cross-sections: min. 0.25 mm
2
/ max. 2.5 mm
2
■
■
Max. cable length: 50 m
■
■
Do not connect any external power sources.
Procedure
1. Remove the cover of the inverter as described in Section 5.1.1.
– Do not remove any contact protection.
2. Route the cable through the middle cable gland (Figure 27 / 1).
3. Connect the wires as follows:
– Wire stripping length: 7 mm
– Ensure the polarity is right
Contact
Description
S0+
Pulse input (plus pole)
S0–
COM (minus pole)