en
49
Parameter
Description
Value range
Unit
Enable threshold
Activation value
1 000 … 10 000
W
Disable threshold
De-activation value
1 000 … 10 000
W
Enable delay
Activation delay
0 … 60
min
Start time
Activation time
00:00 … 23:59
hh:mm
End time
De-activation time
5. Use MaxTalk 2 Pro to configure the S0 interface (energy counter).
Procedure using MaxTalk 2
1. Start MaxTalk 2
2. Connect MaxTalk 2 to the inverter.
3. Select the inverter in the plant tree.
4. In the "Device" menu, click "Settings". The "Settings" tab will be opened.
5. In the “Mode” menu (Multi-function relay) select the "PacEm" setting.
6. Configure the parameters.
6362 Configuring the "Pac inverter" operating mode
The "Pac inverter" operating mode for the control of self-consumption can be configured
to suit the user's requirements. The functionality is illustrated in Figure 38.
5000
4000
3000
2000
1000
0
t
Pac [W]
Disable threshold
Enable delay
On
Off
Status of
multi function relay
Status of multi function relay [on/off]
Output of the inverter - Pac [W]
Start time
End time
Enable threshold
Figure 38 "Pac inverter" operating mode
The time window of the control of self-consumption is defined by the "Start time" and
"End time" parameters. Outside this time window the inverter's control of self-consump-
tion is inactive.