54
Function /
parameter
Description
Unit / status
GFMMIN2
Checking the minimum permissible mains fre-
quency (limit 2)
-
GFMMIN2-ENA
GFMMIN2 function status
Disabled/enabled
GFMMIN2-THR
Limit value
Hz
GFMMIN2-DLY
Trip time
s
GFMMAX2
Checking the maximum permissible mains fre-
quency (limit 2)
-
GFMMAX2-ENA
GFMMAX2 function status
Disabled/enabled
GFMMAX2-THR
Limit value
Hz
GFMMAX2-DLY
Trip time
s
AIS
Detection of island operation
-
AIS-ENA
AIS function status
Disabled/enabled
AIS-DLY
Trip time
s
RBCM
Monitoring the continuous leakage current
-
RBCM-ENA
RBCM function status
Disabled/enabled
RBCM-THR
Maximum permissible leakage current
A
RSCM
Monitoring the leakage current step value
-
RSCM-ENA
RSCM function status
Disabled/enabled
DCCIM
Monitoring the DC component in the AC current
-
DCCIM-ENA
DCCIM function status
Disabled/enabled
DCCIM-THR
Maximum permissible DC component in AC current A
DCCIM-DLY
Trip time
s
Limitation
Functions and parameters of the "Limitation" sub-menu:
Function /
parameter
Description
Unit / status
ACPPL
Maximum increase of the active power during grid
connection
-
ACPPL-ENA
ACPPL function status
Disabled/enabled
ACPPL-MGDT
Increase
% of Pac nom/
min
ACPPL-INI
ACPPL at every start-up
Disabled/enabled
ACPPL-RCN
ACPPL at boot after grid disconnection through
coupler breaker
Disabled/enabled
ACPL
Limitation of active output power
-
ACPL-LMT
Limit value
W
APPL
Limit of the apparent power
-
APPL-LMT
Limit value
VA
OCL
Limitation of the output current
-
OCL-LMT
Limit value
A