74
SM4TP
SM5TP2
SM6TP2
SM7TP2
Components
Display
Graphics display with backlighting and status LED
Inverter topology
transformerless
DC disconnector
integrated
Data logger
Energy yields, peak output and operating duration of the
last 31 days, 12 months, 10 years / output curves of the
last 7 days
Fault current monitoring
Internal, AC/DC sensitive
Casing / cover
Aluminum / plastic ASA+PC
Overvoltage conductor DC/AC
Requirement class D (VDE 0675-6) and/or type 3 (EN
61643-11)
Standards &
guidelines
CE-compliant
Yes
3)
EMC
EN 61000-3-2 / EN 61000-3-3 / EN 61000-6-2 / EN
61000-6-3
Grid connection
VDE 0126-1-1 (A1: 2012 / 2013) / VDE-AR-N 4105
UTE C15-712-1 / E8001-4-712
Device safety
IEC/ EN 62109-1/ -2
Interfaces
Data communication
RS485 / Ethernet (Plug&Play)
Status signalling contact
integrated
Ripple control signal receiver
integrated
External lightning protection
monitor
integrated
External grid monitoring
integrated
Energy counter
S0
Weight &
dimensions
Weight
20kg
21kg
21kg
21kg
Dimensions (W x H x D)
476 x 360 x 180 mm
Warranty
Standard 5 years / extension to 10, 15, 20 or 25 years possible
1) for rated output power and symmetrical layout of the PV generator
2) different values are possible depending on the country setting selected; for further information visit www.
solarmax.com
3) the complete conformity declaration can be found on our website at www.solarmax.com
Country-specific settings
The factory’s default settings for different countries can be viewed in the technical infor-
mation “SSF - Standard specific functions and parameters”. This document can be down-
loaded from our website at: www.solarmax.com; Downloads / String inverters / TP series.