en
73
11 Specifications
SM4TP
SM5TP2
SM6TP2
SM7TP2
Input values
MPP voltage range
1)
420…750 V 260…750 V 310…750 V 360…750 V
Control range
250…840 V 250…840 V 250…840 V 250…840 V
Minimum DC voltage
250 V
250 V
250 V
250 V
Maximum DC voltage
900 V
900 V
900 V
900 V
Maximum DC current
10 A
10 + 10 A
10 + 10 A
10 + 10 A
Number of MPP-Trackers
1
2
2
2
Max. PV generator output
power per MPP tracker
5 000 Wp
5 000 Wp
5 000 Wp
5 000 Wp
Number of string connections
1
2
2
2
Connection type
Wieland PST40i1 (identical to MC4)
Overvoltage category
II
Output values
Rated output power
2)
4 000 W
5 000 W
6 000 W
7 000 W
Maximum apparent output
power
2)
4 000 VA
5 000 VA
6 000 VA
7 000 VA
Maximum AC current
2)
3 x 6.5 A
3 x 7.5 A
3 x 9.5 A
3 x 10.2 A
Nominal mains voltage /
range
3 x 400 V
Mains nominal frequency
/ range
50 / 45…55 Hz
Power factor cos
φ
Adjustable from 0.8 overexcited to 0.8 underexcited
Distortion factor at rated
power
< 3 %
Connection type
Terminal 2.5 - 10 mm
2
Grid connection
Three-phase (L1 / L2 / L3 / N / PE)
Overvoltage category
III
Power input at night
< 0.1 W
Efficiency
Maximum efficiency
97.5 %
97.6 %
97.6 %
97.6 %
Europ. Efficiency
96.0 %
96.5 %
96.6 %
96.7 %
Environment
Protection type
IP 65
Ambient temperature range
(for rated power output)
−20…+60 °C (−20…+45 °C)
Relative humidity
0…100% (condensation)
Max. operating level above
sea level
2000 m
Fire protection class
UL94 V0
Environmental category
In the open
Suitable for wet rooms
Yes
Level of pollution
3