6�4�4 Configuring the status signaling contacts
The two status signaling contacts for the remote monitoring of the inverter can be con-
figured in four different ways.
Procedure
1. In the "Settings" menu, select the "Status relay" parameter.
2. Make the required setting:
Setting
Description
Off
The status signaling contacts are always open.
Grid
When the inverter starts mains operation, the status signaling con-
tacts close and remain closed for as long as the inverter feeds into
the grid. When a power unit (MPP tracker 1/2 or MPP tracker 3/4) is
disconnected from the grid, the respective status signaling contact
opens after an adjustable delay time.
Error
When a warning, a failure or a device error occurs at a power unit
(MPP tracker 1/2 or MPP tracker 3/4) (error messages, see Section
8.2), the respective status signaling contact closes after the expiry
of the adjustable delay time. The status signaling contact opens
when the error has been eliminated (factory setting).
On
When a power unit (MPP tracker 1/2 or MPP tracker 3/4) switches
on when the DC input voltage is sufficiently high, the respectie
status signaling contact closes. The status signaling contact opens
when the power unit switches off due to insufficient DC input
voltage.
3. Select the "Status relay delay" parameter.
4. Adjust the required delay time for the status signaling contacts:
Parameter
Description
Value range
Unit
Status relay delay
Delay time of status signaling contact
0 to 99
min
6�5
Displaying the configuration
All available operating parameters, standard-specific functions and their parameteriza-
tion can be retrieved in the "Configuration" menu. Configuration of the standard-specific
functions depends on the country setting selected.
Note
The MaxTalk 2 Pro service and communication software makes it possible
for authorized personnel to individually adjust the operating parameters (see
Section 12).
Summary of Contents for SM30HT4
Page 1: ...Instruction manual SolarMax HT series 30HT4 32HT4...
Page 10: ...10 3 4 Dimensions mm 590 580 397 847 871 Figure 1 Dimensions with wall mounting bracket...
Page 11: ...en 11 3 5 Views of the unit 2 3 4 12 11 9 10 8 7 7 6 1 5 Figure 2 Views of the unit...
Page 74: ...SolarMax Service Center hotline solarmax com www solarmax com service 2014 05 en...