Grid operation
Functions and parameters of the "Grid operation" sub-menu:
Function /
parameter
Description
Unit / status
GVMMIN1
Checking the minimum permissible mains voltage
(limit 1)
-
GVMMIN1-ENA
GVMMIN1 function status
Disabled/enabled
GVMMIN1-THR
Limit value
V
GVMMIN1-DLY
Trip time
s
GVMMAX1
Checking the maximum permissible mains voltage
(limit 1)
-
GVMMAX1-ENA
GVMMAX1 function status
Disabled/enabled
GVMMAX1-THR
Limit value
V
GVMMAX1-DLY
Trip time
s
GVMMIN2
Checking the minimum permissible mains voltage
(limit 2)
-
GVMMIN2-ENA
GVMMIN2 function status
Disabled/enabled
GVMMIN2-THR
Limit value
V
GVMMIN2-DLY
Trip time
s
GVMMAX2
Checking the maximum permissible mains voltage
(limit 2)
-
GVMMAX2-ENA
GVMMAX2 function status
Disabled/enabled
GVMMAX2-THR
Limit value
V
GVMMAX2-DLY
Trip time
s
GVM10AMAX
Checking the maximum permissible average value
for mains voltage over the last 10 minutes
V
GVM10AMAX-ENA
GVM10AMAX function status
Disabled/enabled
GVM10AMAX-THR
Limit value
V
GVM10AMAX-DLY
Trip time
s
GVMT
Monitoring for unacceptably high peaks in the
mains voltage.
-
GVMT-ENA
GVMT function status
Disabled/enabled
GFMMIN1
Checking the minimum permissible mains fre-
quency (limit 1)
-
GFMMIN1-ENA
GFMMIN1 function status
Disabled/enabled
GFMMIN1-THR
Limit value
Hz
GFMMIN1-DLY
Trip time
s
GFMMAX1
Checking the maximum permissible mains fre-
quency (limit 1)
-
GFMMAX1-ENA
GFMMAX1 function status
Disabled/enabled
GFMMAX1-THR
Limit value
Hz
GFMMAX1-DLY
Trip time
s
Summary of Contents for SM30HT4
Page 1: ...Instruction manual SolarMax HT series 30HT4 32HT4...
Page 10: ...10 3 4 Dimensions mm 590 580 397 847 871 Figure 1 Dimensions with wall mounting bracket...
Page 11: ...en 11 3 5 Views of the unit 2 3 4 12 11 9 10 8 7 7 6 1 5 Figure 2 Views of the unit...
Page 74: ...SolarMax Service Center hotline solarmax com www solarmax com service 2014 05 en...