Connecting the inverter to the mains
DANGER!
Fatal electric shock hazard!
■
■
Make sure the AC input conductor is not live during connection work.
Connection conditions
■
■
Comply with the connection conditions set by the grid operator.
■
■
M40 cable gland; suitable for cable
Ø
: 24 to 33 mm
■
■
Connection type: screw terminals (UWV 25)
■
■
Permissible conductor cross sections:
– flexible conductor (with or without conductor sleeve): max. 25 mm
2
– rigid conductors: max. 35 mm
2
■
■
The protective conductor of the AC input conductor should be cut at least 30 mm
longer than the other conductors.
■
■
The AC input conductor must be fused. Minimum conductor cross sections and sug-
gested mains fuses:
Minimum conductor cross sections
30HT4
32HT4
Phases L1, L2, L3
10 mm
2
10 mm
2
Neutral conductor N
4 mm
2
4 mm
2
Protective conductor PE
10 mm
2
10 mm
2
Recommended mains fuses
30HT4
32HT4
Nominal current
63 A
63 A
Characteristics
C
C
■
■
Make sure the ambient temperatures for the mains fuses specified by the producer
are not exceeded.
WARNING!
Fatal fire risk!
■
■
Provide separate fuses for each inverter.
■
■
Do not connect any loads between the inverter and the mains fuse.
■
■
If you use external residual current devices (RCDs), use the type B RCDs with a nom-
inal fault current of 100 mA. For PV plants with large stray current capacities, the
RCDs to be used should have a nominal fault current capacity of 300 mA.
Procedure
1. Remove the cover of the inverter as described in section 5.1.
2. Thread the AC input conductor through the cable gland.
Summary of Contents for SM30HT4
Page 1: ...Instruction manual SolarMax HT series 30HT4 32HT4...
Page 10: ...10 3 4 Dimensions mm 590 580 397 847 871 Figure 1 Dimensions with wall mounting bracket...
Page 11: ...en 11 3 5 Views of the unit 2 3 4 12 11 9 10 8 7 7 6 1 5 Figure 2 Views of the unit...
Page 74: ...SolarMax Service Center hotline solarmax com www solarmax com service 2014 05 en...