5.4.2 Connecting the DC feed line to the MCU
The connection to the DC voltage of the PV generator ensures uninterrupted operation
of the MCU in the case of a failure of the AC mains. In addition, the connection permits
measuring the DC voltage by the MCU.
Cable requirements
2 x minimum 2.5 mm
2
(900 V
DC
)
Procedure
1. Connect the cable to the terminals “DC+” and “DC−” within the MCU. Position of the
terminals, see 5.4.1 “Interior view of the MCU”.
2. Connect the cable to the fuse holders “DC+” and “DC−” within the nearest inverter.
Make sure the polarity is right. Position of the fuse holders: see 5.3.1 “Interior view of
the inverter”.
DC+
DC
5.4.3 Connecting the AC feed line to the MCU
The autonomous power supply transformer or an available 230 V mains supplies the AC
power to the MCU.
Cable requirements
■
■
Supply voltage: 230 V
AC
■
■
Maximum power consumption: 60 W
■
■
Three-core cable; L1, N and PE (230 V); 3 x minimum 1 mm
2
Procedure
Connect the cable to the terminals L1, N, and PE within the MCU. Position of the terminals:
see 5.4.1 “Interior view of the MCU”.